When a duct high limit option is ordered, DRI-STEEM provides
either a duct high limit switch or a duct high limit humidity
transmitter (4 to 20 mA output, 0 to 100% RH range) for duct
mounting.
Duct high limit switch option
The duct high limit switch prevents duct saturation by turning
off the humidifier when reaching the device set point. When this
occurs, a “Duct HL trip” message appears in the Messages Log and
autoclears when duct RH drops below the duct high limit set point.
Modulating high limit transmitter option
The modulating high limit transmitter operates in conjunction
with the room/duct controlling transmitter or demand signal
through the Vapor-logic4 control system to prevent excess
humidification in the duct. Vapor-logic4 starts lowering the
humidifier output when the duct relative humidity is within a user-
defined percentage (default is 5%) of the duct high limit set point.
This value is called the duct high limit span and is defined during
Setup.
When duct relative humidity enters this range, a “Duct HL span”
message appears in the Messages Log and the Message label lights
on the keypad/display. If necessary, the reduction of the humidifier
output continues until maximum high limit set point is reached,
shutting off the humidifier completely. If this occurs, a “Duct HL
trip” message appears in the Messages Log.
When the high relative humidity starts to decrease in the duct,
Vapor-logic4 slowly starts to increase steam production. When
the duct relative humidity decreases to greater than the defined
percentage below the duct high limit set point, the control
transmitter or signal by others demand signal is restored as
the primary controller, returning the control system to normal
operation, and the messages in the Messages Log automatically
clear.
Temperature compensation control option
Note: This option is not applicable for XT humidifiers.
When selected as an option, DRI-STEEM provides a temperature
compensation transmitter. The temperature compensation
transmitter continually monitors interior window glass
temperature and transmits this temperature to Vapor-logic4.
Vapor-logic4 assumes a 70 °F (21 °C) room temperature and uses
the glass temperature and the RH in the space being controlled to
calculate the dew point (°F or °C) for the space.
Operation
0QUJPOTBOEGFBUVSFT