VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
Piping:
DC-1160
DC-1138
mc_050610_1345
Note:
Use a condensate pump rated for your application. Pumps are rated by
fluid temperature, head (pressure), and flow (gpm). Contact your local
DriSteem representative for pump selection.
Funnel
Condensate pump
Check valve
Frame drain
Tank drain
Discharge piping by installer
mc_050610_1335-w/frame-drain
Drane-kooler
FIGURE 13-1: DRANE-KOOLER FIELD PIPING CONNECTIONS
Tank drain
Frame drain
Hot drain water inlet, 1" (DN25)
Union
Union
Vacuum breaker
Tempered water overflow 12
gpm (45.4 lpm) 140°F (60°C)
Tempered water outlet, 2" (DN50)
Union
Drane-kooler
Part No. 902205 (NPT connections)
Part No. 902206 (BSP connections)
Suppy water inlet, 3/8" (DN10) 25
to 80 psi (172 to 552 kPa) Maximum
temperature 70 °F (21 °C)
Supply water shut-off valve
Notes:
• Dashed lines indicate provided by installer.
Total length of pipe between humidifier and
Drane-kooler not to exceed 10' (3 m).
Field piping
Floor
FIGURE 13-2: LIFTING DRAIN WATER