VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
As steam is discharged from the SDU-E, it quickly cools and turns to a visible
fog that is lighter than air. As this fog is carried away from the SDU-E by the
airstream, it tends to rise toward the ceiling. If this fog contacts solid surfaces
(columns, beams, ceiling, pipes, etc.) before it disappears, it could collect and
drip as water. The greater the space relative humidity, the more the fog will
rise, throw and spread.
Table 27-1 lists the minimum rise, throw and spread non-wetting distances
for SDU-E at 40%, 50% and 60% RH in the space. Surfaces cooler than
ambient temperature, or objects located within this minimum dimension, can
cause condensation and dripping. To avoid steam impingement on surrounding
areas, observe the minimum non-wetting distances in Table 27-1.
The SDU-E contains a blower (120 V, single-phase, 60 Hz) and an airflow
proving switch (field-wired to the humidifier electrical panel). A wiring diagram
of the SDU-E is included with the unit.
On a call for humidity, the humidifier begins producing steam, and the start
relay energizes the SDU-E blower. When the call for humidity is satisfied, the
Vapor-logic controller keeps the blower running to disperse residual moisture
using a time delay.
mc_042710_1255
Steam outlet
Throw
Spread
Air intake grille
DC-1027
Rise
mc_042710_1435
SDU-E RISE, SPREAD, AND THROW
Dispersion: SDU-I and SDU-E
FIGURE 26-1: SDU-E RISE, SPREAD, AND THROW