Page 14 • DRI-STEEM Vaporstream humidifier
Vaporstream VLC piping:
Standard water
Figure 14-1:
Field piping overview, Vaporstream VLC with standard water
Table 14-1:
Heights required to overcome Vaporstream internal pressure
(H1, H2)
Unit output
Water seal height
(H1)
Air vent height
(H2)
kW lbs/hr kg/h inches mm inches mm
≤ 48 ≤ 138 ≤ 62 12 305 22.5 572
49-64 139–183 63–83 15 381 27.5 699
> 64 > 183 > 83 18 457 30.5 775
mc_022310_1325
Notes:
Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces.
Refer to governing codes for drain pipe size and maximum discharge water temperature.
Offset humidifier from floor drain to prevent flash steam from rising into the humidifier.
Dashed lines indicate provided by installer.
The water supply inlet is more than 1" (25 mm) above the skim/overflow port, eliminating the possibility of backflow or siphoning from the tank. No
additional backflow prevention is required; however, governing codes prevail.
Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty.
VLC-OM-010
Figure 14-2:
Piping, Vaporstream VLC with standard
water, Models 2-1 through 5-1
OM-4005
Drain piping
Drain valve
Fill valve
Overflow port
Install level
Install level
¾" (DN20) minimum condensate drain
piping rated for 212 °F (100 °C)
Air vent height
must be equal to
or greater than
dimension H2
(see Table 14-1).
Air vent
tube
Optional condensate
return piping from
dispersion unit
Steam outlet
Shock arrester recommended to reduce water hammer
¾" (DN20) min. drain, skim, and overflow
piping rated for 212 °F (100 °C)
Manual or electric drain valve
If run is over 10' (3 m), increase
pipe to 1¼" (DN32)
Flow line of drain piping after water seal
must be below drain valve to ensure
humidifier drains correctly.
1" (25 mm) air gap
Drain piping
flow line
¾" pipe thread
(DN20) dispersion
unit condensate
return inlet
Pitch 1/8"/ft (1%)
6"
(150 mm)
minimum
Open drain required. See first note below.
Water supply line; water pressure 25 to 80 psi (172 to 552 kPa);
water conductivity 100 μS/cm minimum. If water piping to
humidifier is nonmetallic, first 3' (1 m) of water supply piping from
humidifier should be metallic. To isolate steam from nonmetallic
supply piping, put a 2" (50 mm) water seal or loop in supply line.
See H1 in
Table 14-1
H1
mc_022310_1255
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 31 32

Comments to this Manuals

No comments