
Page 8 • DRI-STEEM Vaporstream humidifier
Vaporstream capacities and electrical
specifications
Table 8-1:
Vaporstream VLC capacities and electrical specifications, standard water and DI/RO water
Model
(kW-
stages)
Maximum
steam
capacity †
Heaters
Current draw (amps)
kWSingle-phase Three-phase***
lbs/hr kg/h Qty.
Stages**
120V 208V* 240V* 277V* 480V* 600V* 208V* 240V* 277V* 480V* 600V*
2-1 5.7 2.6 1 1 16.7 9.6 8.3 7.2 4.2 3.3 —————2
3-1 8.6 3.9 1 1 25.0 14.4 12.5 10.8 6.3 5.0 —————3
4-1 11.4 5.2 1 1 33.3 19.2 16.7 14.4 8.3 6.7 —————4
5-1 15.2 6.9 1 1 44.4 25.6 22.2 19.2 11.1 8.9 —————5.33
6-1 17.1 7.8 3 1 — 28.8 25.0 21.7 12.5 10.0 16.7 14.4 12.5 7.2 5.8 6
9-1 25.7 11.7 3 1 — 43.3 37.5 32.5 18.8 15.0 25.0 21.7 18.8 10.8 8.7 9
12-1 34.2 15.5 3 1 — — — 43.3 25.0 20.0 33.3 28.9 25.0 14.4 11.5 12
16-1 45.6 20.7 3 1 ————33.3 26.7 44.4 38.5 33.3 19.2 15.4 16
21-1 59.9 27.2 3 1 ————43.8 35.0 — — 43.8 25.3 20.2 21
25-1 71.3 32.3 3 1 — ————41.7 — — — 30.1 24.1 25
12-2 34.2 15.5 6 2 — 57.7 50.0 43.3 25.0 20.0 33.3 28.9 25.0 14.4 11.5 12
18-2 51.3 23.3 6 2 — 86.5 75.0 65.0 37.5 30.0 50.0 43.3 37.5 21.7 17.3 18
24-2 68.4 31.0 6 2 — — — 86.6 50.0 40.0 66.6 57.7 50.0 28.9 23.1 24
32-2 91.2 41.4 6 2 ————66.7 53.3 88.8 77.0 66.7 38.5 30.8 32
42-2 119.7 54.3 6 2 ————87.5 70.0 — — 87.5 50.5 40.4 42
50-2 142.5 64.6 6 2 —————83.3 — — — 60.1 48.1 50
18-3 51.3 23.3 9 3 — 86.5 75.0 65.0 37.5 30.0 50.0 43.3 37.5 21.7 17.3 18
27-3 77.0 34.9 9 3 — 129.8 112.5 97.5 56.3 45.0 74.9 65.0 56.3 32.5 26.0 27
36-3 102.6 46.5 9 3 — — — 130.0 75.0 60.0 99.9 86.6 75.0 43.3 34.6 36
48-3 136.8 62.1 9 3 ————100.0 80.0 133.2 115.5 100.0 57.7 46.2 48
63-3 179.6 81.5 9 3 ————131.3 105.0 — — 131.3 75.8 60.6 63
75-3 213.8 97.0 9 3 —————125.0 — — — 90.2 72.2 75
24-4 68.4 31.0 12 4 — 115.4 100.0 86.6 50.0 40.0 66.6 57.7 50.0 28.9 23.1 24
36-4 102.6 46.5 12 4 — 173.1 150.0 130.0 75.0 60.0 99.9 86.6 75.0 43.3 34.6 36
48-4 136.8 62.1 12 4 — — — 173.3 100.0 80.0 133.2 115.5 100.0 57.7 46.2 48
64-4 182.4 82.7 12 4 ————133.3 106.7 177.6 154.0 133.4 77.0 61.6 64
84-4 239.4 108.6 12 4 ————175.0 140.0 — — 175.1 101.0 80.8 84
100-4 285.0 129.3 12 4 —————166.7 — — — 120.3 96.2 100
* If using an optional SDU or Area-type fan unit for dispersion, run a neutral line with 208V/240V/single-phase and 208V/three-phase power supply lines to provide
a 120V circuit for the fan. With all other power supply voltages (other than 120V), provide a separate 120V circuit for the fan, or order from DRI-STEEM a trans-
former installed in the control cabinet.
** Heater stage identifies the number of contactors.
*** Three-phase power supply connection. All heater loads are wired Delta.
† Total humidifier load = load to meet design conditions + load to compensate for steam loss from the dispersion assembly and interconnecting piping. If total
humidifier load is more than the humidifier's maximum capacity, design conditions will not be met. For steam loss data see the
DRI-STEEM Design Guide
available for downloading and printing at www.dristeem.com
mc_021010_0445
Comments to this Manuals