CONTROL CABINET INSTALLATION
The VAPOR-LOGIC control board is shipped mounted
with all internal wiring completed within a control
cabinet. All software has been custom programmed into
your VAPOR-LOGIC system according to the original
order requirements. Refer to the
VAPOR-LOGIC control board drawing for detail of the
board and connection points. (See figure 14-1 on page
14.)
The VAPOR-LOGIC control board should always be
wired following local electric codes. VAPOR-LOGIC is
powered by a low voltage control transformer. The
transformer provides a 24 VAC supply, and is protected
by an integral manual reset circuit breaker.
All humidifier power wiring is represented on the
humidifier wiring diagram.* Follow field wire torque
requirements shown on the humidifier wiring diagram
when connecting the power and control wiring inside
the humidifier control cabinet. Additional precautions
about VAPOR-LOGIC control board connections are:
• Use 3 mm straight blade screwdriver on
VAPOR-LOGIC control board terminal blocks.
• DRI-STEEM recommends a single 1.0 mm
2
pre-tinned wire in each terminal at the
VAPOR-LOGIC terminal block. Torque to 0.1 Nm.
• When terminating multiple wires to VAPOR-LOGIC
control board terminal blocks, DRI-STEEM
recommends securing the multiple wires and one
additional wire with appropriately sized wire nut. Use
the single additional wire's opposite end to connect to
the VAPOR-LOGIC terminal block.
• Never run control system wires bundled with, or in
the same conduit as, power wires.
• Pick a location that will allow for easy access to the
control cabinet and internal electrical components.
Mount control cabinet using the mounting tabs.
IMPORTANT: Locate the control cabinet so that
wire lengths are 15 metres or less to the
humidifier.
*A wiring diagram and installation guide is attached to
the inside of control cabinet door. All instructions
should remain with the control cabinet after
installation.