DriSteem Vapor-Logic Installation Guide Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
34
(1) Modulation type control
(2) Modulation type control with VAV option
(3) Modulation type control with % RH offset option
(4) VPC Series with Auto-Drain feature
(5) Modulation type control with PID control option feature
MAIN MENU
READ-OUT
MAIN MENU
DESCRIPTION
RANGE DEFAULT
AUTO
SCROLL
AUTO SCROLL
READ-OUT
"SET CYC TIME"
(TP Type Control)
Cycle Time (1) 15-99 seconds 60 seconds no
"SET CYC TIME"
(SCR Type
Control)
Cycle Time (1) 4-99 seconds 4 seconds no
"SET DLY TIME"
Multiple Heater Delay
Time (1)
4-99 seconds 20 seconds no
"SET KP" Proportional Band (5) 100-1000 10% (200) no none
"SET KI"
Integral Gain Factor
(5)
50-500
5%
(250)
no none
"SET KD"
Derivitive Gain Factor
(5)
0-500 0 (000) no none
"SET SMPL INT" Sample Interval (5)
5-1200
seconds
0030
(30 seconds)
no none
AUTO SCROLL
DESCRIPTION
AUTO
SCROLL
AUTO SCROLL
READ-OUT
Heater One
Demand %
yes "K1 DEMAND: %"
Heater Two
Demand %
yes "K2 DEMAND: %"
Heater Three
Demand %
yes "K3 DEMAND: %"
Heater Four
Demand %
yes "K4 DEMAND: %"
Total System
Demand %
yes "SYS DEMAND:%"
Steam Ouput
(kg/hr)
yes "SYS OUT: KG/HR"
MAIN MENU/AUTO SCROLL INFORMATION
Page view 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 51 52