12
pad will display “LOW WATER” as part of auto scroll
text.
11. Airflow switch input must be closed.
12. High limit humidistat input must be closed or
Variable Air Volume (VAV) control system high limit
transmitter must be connected.
13. If aquastat option is furnished, connections to
terminals #16 and #17 are necessary.
14. With sufficient water in tank, (on some newer
models a green LED lamp on the control board will be
illuminated), airflow switch closed, high limit humidistat
closed, and a call for humidity, the heater outputs will
be energized. If the tank does not contain water and
the heaters are energized by the VAPOR-LOGIC
control system, a serious failure will result. Immediately
remove power from the system and verify that all wiring
is done per the wiring instructions in this manual and
the unit wiring diagram.
15. During normal operation, the key pad will display
auto scroll features of humidifier operating status. See
pages 30 and 31 for descriptions.
16. To change any of the operating parameters,
depress the “MODE” key on key pad to activate the
VAPOR-LOGIC main menu. Use the up-down arrow
keys to select a main menu item. Press ENT key to
allow you to change the operating parameters. Refer to
pages 21 and 22 for a complete description and pages
30 and 31 for all the other possible main menu items.
17. If necessary to restart VAPOR-LOGIC, depress
the reset button on the electrical sub-panel, hold for a
few seconds, then release.
1. Confirm that the control signal being connected to
the VAPOR-LOGIC
®
system is compatible with the
VAPOR-LOGIC program. Identify the VAPOR-LOGIC
program code on the wiring diagram or on the outside
of control cabinet door. Refer to the VAPOR-LOGIC
Manual to decipher the code using the nomenclature
description on page 3.
2. Confirm all wiring is correct per wiring diagram.
3. Confirm that proper grounding and an approved
earth ground are provided.
4. Confirm J9, J10, J11 shunt connectors on
VAPOR-LOGIC board are in their correct position per
wiring diagram. See page 14 for the physical locations.
5. Confirm four position slide switch on
VAPOR-LOGIC board is in “AUTO” position.
6. Confirm that the digital key pad is mounted on the
outside of the control cabinet with modular cable routed
away from the high voltage circuits and connected to
either J1 or J2 female connector on control board.
7. Turn water supply on, confirm drain valve is closed.
8. Turn power on, the key pad will display the
introduction of “VAPOR-LOGIC”, transfer into
INITIALIZING, and the enter into AUTO mode. In
AUTO mode, the system will continuously scroll system
operations status (see pages 33 and 34).
9. In normal operation, the red LED lamp on
VAPOR-LOGIC board will blink off-on like a heart beat.
(In fault mode, the red LED lamp will blink a pulse
code.)
10. System will initiate filling of the tank with water, key