Supply water and drain piping
Supply water piping may be of any code-approved material (copper,
steel, or plastic). The fill valve connection size is a ¼" pipe thread
(DN8) fitting except in Europe where it is a DN10 pipe thread
fitting. In cases where water hammer may be a possibility, consider
installing a shock arrestor. Water pressure must be between 25 psi
and 80 psi (175 kPa and 550 kPa).
If water piping to humidifier is nonmetallic, we recommend that
the first 3' (1 m) of water supply piping from the humidifier be
metallic with a 2" (50 mm) water seal or loop in the supply line to
isolate steam from nonmetallic supply piping.
Drain piping may be of any code-approved material (copper,
steel, or plastic rated for 212 °F [100 °C] minimum). If drainage
by gravity is not possible, use a reservoir pump rated for 212 °F
(100 °C) water (DRI-STEEM Part No. 400280 for 120V pump and
Part No. 400281 for 230V pump).
The final connection size is ¾" (DN20) copper for the tank and
frame drains. Do not reduce this connection size. Pipe the tank and
frame drains separately, as shown in Figures 8-1 and 9-1, to prevent
backflow of drain water into the humidifier cabinet.
If the equivalent length of pipe from the humidifier drain to the
plumbing system drain is more than 10' (3 m), increase the pipe
size to 1¼" (DN32).
See Figures 8-1 and 9-1 for more piping instructions.
Important: Install unions in the water supply and drain lines as
shown in Figures 8-1 and 9-1 to allow tank removal.
4VQQMZXBUFSBOEESBJOQJQJOH
WARNING!
Opening the drain valve when the tank is hot
can discharge water with a temperature up
to 212 °F (60 °C) into the plumbing system.
This can cause damage to the plumbing
system if the humidifier is not properly
connected to a water tempering device such
as a DRI-STEEM Drane-kooler™.
Do not touch the tank or drain piping until
the unit has had sufficient time to cool, or
serious injury can occur.
Figure 10-1:
Drane-kooler water tempering device
DRI-STEEM's Drane-kooler, shown mounted
to a Vapormist humidifier, tempers
discharged water. For other Drane-kooler
mounting options or for more information,
contact your DRI-STEEM representative/
distributor, or view the Drane-kooler
product data sheet in the literature section
at www.dristeem.com
OM-7398
VM-IOM-1108.pdf 12 4/21/2010 1:36:20 PM
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 47 48

Comments to this Manuals

No comments