%3*45&&.7BQPSNJTU&MFDUSJD)VNJEJGJFS*OTUBMMBUJPO0QFSBUJPOBOE.BJOUFOBODF.BOVBMt1BHF
Rapid-sorb pitch requirements
t 8IFOJOTUBMMJOHB3BQJETPSCXJUIUIFIFBEFSPVUTJEFB
horizontal airflow duct, consider the following pitch issues:
For 1½" (DN40) dispersion tubes use a fastener of sufficient
length to accommodate the 1/8"/ft (1%) pitch requirements
toward the ¾" pipe thread (DN20) header drain fitting.
For 2" (DN50) dispersion tubes, the bracket can be mounted
flush to the ductwork. The 1/8"/ft (1%) pitch typically can be
accomplished in the length of the hose cuffs used to connect
the tubes to the header.
t 4FFUIFUBCMFCFMPXBOEUIFESBXJOHTPOUIFGPMMPXJOHQBHFTGPS
pitch requirements.
Table 25-1:
Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb evaporative dispersion units
Airflow
Type of
interconnecting piping
Diameter of
interconnecting piping
Pitch of
interconnecting piping
Pitch of
dispersion tubes
Pitch of
header
Horizontal
Vapor hose
1½" (DN40)
2" (DN50)
2"/ft (15%)
toward
Rapid-sorb
Vertically
plumb
1/8"/ft (1%)
toward
condensate
drain
Tubing or pipe
1½" (DN40)
2" (DN50)
1/8"/ft (1%)
toward
Rapid-sorb
Vertical
Vapor hose
1½" (DN40)
2" (DN50)
2"/ft (15%)
toward
Rapid-sorb 2"/ft
toward
header
1/8"/ft (1%)
toward
condensate
drain
Tubing or pipe
1½" (DN40)
2" (DN50)
1/8"/ft (1%)
toward
Rapid-sorb
%JTQFSTJPO3BQJETPSCDPOUJOVFE