DriSteem VAPORMIST Specifications Page 33

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 32
%3*45&&.7BQPSNJTU&MFDUSJD)VNJEJGJFS*OTUBMMBUJPO0QFSBUJPOBOE.BJOUFOBODF.BOVBMt1BHF
)VNJEJGJFSTUBSUVQQSPDFEVSF
After the system is installed and connected properly, you can begin
start-up procedures.
1. Verify that the Vapormist humidifier, controls, piping, electrical
connections, steam supply, and dispersion assembly(s) are
installed according to the following:
 t *OTUBMMBUJPOJOTUSVDUJPOTJOUIJTNBOVBM
tVapor-logic
3 Installation and Operation Manual
Installation section
Installation checklist
 t -BEEFSTUZMFXJSJOHEJBHSBNJOTJEFIVNJEJGJFSFMFDUSJDBMQBOFM
cover)
 t &YUFSOBMDPOOFDUJPOTXJSJOHEJBHSBNJOTJEFIVNJEJGJFS
electrical panel cover)
 t "MMHPWFSOJOHDPEFT
2. Verify that all electrical connections are secure before applying
power. (See torque requirements on Page 35.)
3. WARNING!
Make sure that all electrical covers are in place and secure before
turning on electrical power. These include the following:
t )FBUFSUFSNJOBMDPWFSPOUBOL
t )VNJEJmFSFMFDUSJDBMQBOFMDPWFS
4. Verify that the humidifier is mounted level and securely
supported before filling with water (see the operating weights
table in this manual).
5. Verify that the humidifier is level front to back and side to side
after it is full of water.
6. Refer to the following sections in the Vapor-logic
3 Installation
and Operation Manual:
 t 0QFSBUJPOTFDUJPO
 t 4UBSUVQDIFDLMJTUJUJTDSJUJDBMUIBUUIFJOTUBMMFSGPMMPXUIJT
checklist)
7. During start-up, do not leave the humidifier unattended.
8. Monitor humidifier operation through multiple fill cycles. The
humidifier operating status appears on the keypad/display.
9. On standard water units, water skims from the humidifier
after every fill cycle. Adjust the amount of skim by increasing
or decreasing the skim time (see the Vapor-logic
3 Installation
and Operation Manual). However, at start-up, DRI-STEEM
recommends initially running the humidifier with the factory
default setting for skim time.
Note:
The
Vapor-logic3 Installation and Operation
Manual
is a comprehensive operation
manual. Refer to it for information regarding
the following features:
t ,FZQBEEJTQMBZTFUVQBOENFOV
information
t $POUSPMJOQVUTJHOBMTBOEGVODUJPOT
t %SBJOGMVTIBOETLJNGFBUVSFT
t 4BGFUZGFBUVSFT
t "MBSNTDSFFOTBOEGBVMUNFTTBHFT
The
Vapor-logic3
manual was shipped with
your humidifier. Additional copies can be
viewed, printed, or ordered at
www.dristeem.com
WARNING!
Only qualified electrical personnel should
perform start-up procedure.
Contact with energized circuits can cause
property damage, severe personal injury or
death as a result of electrical shock or fire.
CAUTION! In the event the humidifier
tank does not contain water and the
heaters are energized, turn main power off.
Operation of the heaters without water will
cause damage to the humidifier. Before
turning main power on, verify that all
wiring has been completed per the wiring
instructions in this manual and the unit
wiring diagrams.
VM-IOM-1108.pdf 33 4/21/2010 1:36:22 PM