DriSteem Vapor-logic3 Operations Instructions Page 30

  • Download
  • Add to my manuals
  • Print
  • Page
    / 75
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 29
28
“Set Up” menu information.
Operation
Operation:
“Set Up” menu information
“Set Up” menu “Set Up” menu Range Default
readout description
RH Set point Relative humidity set point 20-80% RH 35%
RH Offset RH offset calibration ±20% RH 0%
Dewpoint Set point Dew point set point 20-80°F/-7-27°C 50°F/10°C
Dewpoint Offset Dew point offset calibration ±20°F/±20°C 0°F/0°C
PID Band PID loop modulation band 1-20% RH 10%
Kp Proportional gain factor 1-1000 80
Ki Integral gain factor 0-1000 40
Kd Derivative gain factor 0-1000 0
Duct High Lim RH Duct high limit RH set point 50-95% RH 80%Duct
RH Offset Duct RH offset calibration ±20% RH 0%
Temp Comp Offset Temp comp sensor calibration ±20°F/±20°C 0°F/0°C
ADS Mode ADS operating mode Use Use
Use + Interval
Interval
Lbs of H20 until ADS Lbs/kg of water 6-32,767 lbs/ System
that must be boiled 3-14,863 kg dependent
for ADS to start
ADS Day Day to start ADS sequence Sunday - Saturday 1
Today Current day of the week Sunday - Saturday 1
ADS Hour Hour to start ADS sequence 0-23 0
(midnight–11:00 p.m.)
ADS Interval Number of days 0-180 days 7 days
between ADS cycles
ADS Duration Autodrain sequence duration 0-120 minutes 8 minutes
AFS Duration Auto flush sequence duration 0-15 minutes 8 minutes
Service Setpoint Service interval set point 100-3,276,700 lbs/ System
100-1,486,300 kg dependent
Skim Duration Skim time duration 0-120 seconds 3 seconds
Heater Cycle Time Cycle time 30-99 seconds 60 seconds
(TP-type control)
Heater Cycle Time Cycle time 1-30 seconds 2 seconds
(SSR-type control)
SDU Duration SDU delay duration 1-30 minutes 2 minutes
Aquastat Aquastat set point 40-180°F/4-82°C 40°F/4°C
Inactivity Until EOS Inactivity time until EOS 1-168 hours 72 hours
drain cycle starts
Set Up Password Password required to 0-32767 0
enter the “Set Up” screen (0 = password disabled)
Configuration String See program code nomenclature System dependent System
dependent
Real Time Clock Clock and date settings N/A Current
date/time