Operation:
Fill timer, over-temp fault
Safety features.
Operation
Fill timer
The VAPOR-LOGIC
®
3
controller keeps track of
approximately how much water, in the form of steam,
has left the tank. If this total amount exceeds a preset
limit without the fill valve being energized, a low water
condition is assumed and the humidifier is shut down.
Each time the fill valve is energized, the total is reset
to zero. Note that this system is not used on a DI/RO
humidifier because the fill valve is not an electric-
solenoid type. On a DI/RO tank, a mechanical fill
valve maintains the proper water level. This fill valve
operates independently of the VAPOR-LOGIC
3
controller. Therefore, on a DI/RO system, there is no
way to reset the steam total to zero as the tank fills.
Over-temp fault
The tank temperature is constantly monitored by the
VAPOR-LOGIC
3
controller. If the temperature ever
rises above a preset limit, the humidifier is shut down
and a thermal trip fault is given on the Alarms screen
of the keypad/display. This fault must be cleared or
acknowledged on the Alarms screen by the user
before humidifier operation will resume.