Main menu: 2) Control Modes.
Operation
Control Modes
In the Control Modes screen, the operational mode of
the humidifier can be set. You may choose from auto,
test, manual drain or standby.
In Auto Mode, the humidifier operates normally. All
inputs and outputs are monitored and controlled. If
there is a call for humidification, the system will
react.
In Test Mode, the controller sequentially cycles
through all outputs so that their operation may be
confirmed. Once all outputs have been cycled on and
off, the controller reverts to the Standby Mode.
In Manual Drain Mode, the automatic drain valve
(if so equipped) is opened and the tank is drained. All
humidifier operation is suspended and the drain valve
is held open until the unit is taken out of Manual
Drain Mode.
In Standby Mode, the humidification system is
taken off line. All humidity control inputs are
displayed but not acted upon.
To select a new mode, use the vertical arrow keys to
move the selection pointer on the left hand side of the
screen up or down. When the pointer is positioned
next to your new selection, press the Enter key. Your
new selection will now appear as inverted text.
Note that the current mode of the humidifier is
always shown as inverted text on this screen.