Operation
Diagnostics
The Diagnostics screen enables you to troubleshoot
some of the hardware input and output points of the
VAPOR-LOGIC
®
3
control system. The soft keys Next
and Back are used to move through the diagnostic
options. Once you have found the item you would
like to troubleshoot, view the reading and compare it
with what the value should be.
For example, if you were going to troubleshoot the
RH signal input, you would select RH Signal on the
Diagnostics screen. The display would then tell you
what the current input signal is in mA. It would also
tell you what this voltage translates to in terms of
relative humidity. You can then verify that the input is
working correctly.
Main menu: 5) Diagnostics.
Operation:
Main menu: 5) Diagnostics
Depending on system options and type, diagnostics
available may include:
RH input
Demand input
Dewpoint input
Duct HL input
Temp comp input
High probe voltage
Mid probe voltage
Low probe voltage
DI float
Tank temp input
Air flow switch
Safety interlock
Blower #1 RPM
Blower #2 RPM
Burner #1 gas valve
Burner #2 gas valve
Combustion air switch
Power vent switch
Flue differential pressure switch
Page view 35