Product overview
Expansion board connections.
Product overview:
Expansion board connections
GTS
®
and VAPORSTREAM
®
expansion board
connections
J1 1/4" push-on connector for earth ground
J2 Blower # 2 control:
Terminal 21: Positive polarity 21 VDC supply
(25 mA max)
Terminal 22: Blower tachometer feedback
Terminal 23: PWM output to blower
Terminal 24: Common
J3 Blower # 1 control:
Terminal 17: Positive polarity 21 VDC supply
(25 mA max)
Terminal 18: Blower tachometer feedback
Terminal 19: PWM output to blower
Terminal 20: Common
J5 Ribbon cable connector for VAPOR-LOGIC
®
3
main controller connection
J6 Ribbon cable connector for additional
VAPOR-LOGIC
3
expansion modules
J7 Wire terminal supplies 24 VAC to power the
VAPOR-LOGIC
3
expansion module.
Terminal T1 – 24 VAC, 10 VA maximum
load
Terminal T2 – 24 VAC common
J8 Wire terminal connector supplies 24 VAC voltage
with terminal pairs 1 and 2, 3 and 4, and 5 and 6
to either contactors or GTS ignition controllers.
(Terminals 1, 3 and 5 supply the 24 VAC.
Terminals 2, 4 and 6 provide the 24 VAC
common.)
J9 Wire terminal connection provides optically
isolated connections for the gas valve feedback.
Terminals 7 and 9 provide 24 VAC and are not
used. Terminal 8 receives a 24 VAC signal back
from gas valve #1. Terminal 10 receives a 24
VAC signal back from gas valve #2.
J10 Wire terminal connection provides optically
isolated connections for the combustion air
damper limit switch, power vent pressure switch
and flue differential pressure switch. Terminal 11
supplies 24 VAC to the combustion air damper
limit switch, which closes when the damper has
opened. Terminal 12 is the return connection
from the limit switch into the VAPOR-LOGIC
3
expansion module. Terminal 13 supplies 24 VAC
to the power vent pressure switch which closes
when the fan has started. Terminal 14 is the
return connection from the pressure switch into
the VAPOR-LOGIC
3
expansion module. Terminal
15 supplies 24 VAC to the flue differential
pressure switch which closes when the blowers
have started. Terminal 16 is the return
connection from the differential pressure switch
into the VAPOR-LOGIC
3
expansion module.