DRI-STEEM provides two types of on-off control: wall-mounted
humidistat and duct-mounted humidistat. On-off control can also
be achieved using a signal from another source, such as a building
automation system (signal by others). The wiring diagram (located
on the inside of the humidifier control cabinet) shows proper wiring
for these controls.
Wiring modulating humidistats
When using modulating control, the signal from a humidistat
directly controls the amount of output from the humidifier.
The standard modulating humidistat controllers provided by
DRI-STEEM are either duct mounted or wall mounted.
The humidistats are powered by a 21 VDC supply provided by
the Vapor-logic
3
control board. A variable control signal from the
humidistat modulates humidifier operation.
For a pneumatic modulating signal, DRI-STEEM offers a transducer
that accepts a 3 to 20 psi (21 to 138 kPa) pneumatic input range.
Wiring modulating humidity or temperature transmitters
Transmitters provide an analog signal proportional to the
process variable being measured. All transmitters provided by
DRI-STEEM are two-wire devices. (See your wiring diagram for
proper connections.) The humidity transmitters have a range of
0 to 100% RH with an output of 4 to 20 mA. The temperature
transmitter has a range of –20 °F to 160 °F (–29 °C to 71 °C) with a
4 to 20 mA output.
Installation: Wiring detail
OM-2027b
Figure 27-1:
Control humidity transmitter wiring
Place shunt across
“I˝ pins of J14/17
when connecting
a 4-20 mA
control humidity
transmitter. See
Page 13 for more
information about
KVNQFSQJOT
J14/17
0 – 15 VDC
0 – 20 mA
0 – 150 ohm
RIV
OM-4030
Calculation of transmitter % RH
3)
(mA reading) – 4
0.16
Example:
12 mA – 4
3)
0.16