DriSteem HUMIDI-TECH DI Installation Guide Page 46

  • Download
  • Add to my manuals
  • Print
  • Page
    / 108
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 45
1BHFt%3*45&&.7BQPSMPHJD
3
Installation and Operation Manual
One master controller, multiple slave tanks
Vapor-logic
3
has the capability to operate multiple DRI-STEEM
humidifier tanks under the control of one Vapor-logic
3
controller.
This is called operating in multi-tank mode. A multi-tank system
has the following components:
t 4MBWFIVNJEJGJFSUBOLT
Every humidifier tank in a multi-tank group is called a slave
humidifier tank. Every slave humidifier tank's controller has the
capability to also become a master controller, but only one master
controller per multi-tank system is allowed.
t 0OFNBTUFSDPOUSPMMFS
The master controller receives the demand signal and controls
slave humidifier tank steam production based on:
— Priority group
— Wear leveling
— Fault status
The master controller also gives permission to slave humidifier
tanks to perform functions such as draining and flushing.
To become a master controller, a slave humidifier tank's controller
must be field-wired to all required control input signals and be
programmed with the system capacity.
t 7BQPSMPHJD
3
keypad
There is one Vapor-logic
3
keypad per multi-tank group. This
keypad ships attached to the master controller but it can be
connected to any humidifier in the multi-tank group, mounted
within the maximum keypad cable length (500' [152 m]) from
keypad to any control board in the multi-tank group.
Multiple tank configurations:
Introduction
Important:
Information on this page applies to
Vapor-logic
3
firmware versions 5.x.x
and 7.x.x only (systems with multi-tank
capability).
VL3_IOM.pdf 46 11/19/2009 9:11:14 AM