DriSteem HUMIDI-TECH DI Installation Guide Page 69

  • Download
  • Add to my manuals
  • Print
  • Page
    / 108
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 68
DRI-STEEM Vapor-logic
3
*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
Adjusting set point through the Set Up menu
You can adjust your units set point using the Set Up menu, which
is under the Main menu (see the menu structure diagram on
Pages 54-55).
Once you access the Set Up menu, you can adjust a number
of parameters including the set point of the unit. To adjust the
humidity set point, your unit must be configured for a humidity
transmitter. You can enter a desired humidity set point anywhere in
the range of 20% to 80%. Your set point modifications take effect
as soon as you press Enter, or move to another parameter using the
Next or Back soft keys, or exit the Set Up menu using the Main soft
key.
Depending on your options, you also can adjust the high limit
humidity set point and the dew point set point. The high limit set
point has a valid range of 50% to 95%. The dew point set point has
a valid range of 20 °F to 80 °F (–7 °C to 27 °C).
Adjusting set point
VL3_IOM.pdf 69 11/19/2009 9:11:15 AM