SDU operation
If your humidifier is equipped with a Space Distribution Unit
(SDU) or an Area-type fan, it is enabled after the Vapor-logic
3
receives a call for humidity and the tank temperature rises above
150 °F (66 °C).
When the humidifier no longer receives a call for humidity, it stops
heating and the SDU or Area-type fan continues to run for the SDU
Duration to ensure that steam gets dispersed. The SDU Duration
is adjustable in one-minute intervals (default is 5 minutes) through
the Set Up screen.
Sensor offsets
All external transmitters shipped with Vapor-logic
3
can be field
calibrated using the keypad/display through the Set Up screen. For
example, if the system is equipped with an RH transmitter, there is
an RH offset setting.
The factory default for all transmitter offset settings is zero. If an
adjustment is necessary, use the keypad to adjust the transmitter
reading up or down through this setting. The sensors that have this
adjustment capability are the humidity, VAV high limit, temp comp,
and dew point transmitters.
4%6GBOPQFSBUJPOTFOTPSPGGTFUT