DRI-STEEM Vapor-logic
3
*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
Start-up checklist
Your humidification system may not have all of the options listed
below. If an item does not apply to your system, skip to the next
item and continue the process.
Before you start, read this manual and other information sent
with your humidifier.
Verify that the field wiring is done per the instructions in this
manual and per the unit wiring diagram.
If your humidifier uses potable or softened water (non-DI
water), check probe voltages in the Diagnostics menu. The
reading should be 2.3 VAC without water and 0 VAC with water
from ground (terminal 33 on J8) to probe inputs (terminals 30,
31, and 32 on J8).
Check the heater cycle time setting (except for GTS) in the
System Set Up” menu of the keypad/display (default is 60
seconds; 2 seconds for SSR).
If your system uses an RH transmitter, check the proportional
band setting in the System Set Up menu of the keypad/display
(default is 10%).
If your system uses an RH transmitter, check the proportional
gain (Kp) setting in the System Set Up menu of the keypad/
display (default is 80).
If your system uses an RH transmitter, check the integral gain
(Ki) setting in the System Set Up menu of the keypad/display
(default is 40).
If your system uses an RH transmitter, check the derivative gain
(Kd) setting in the System Set Up menu of the keypad/display
(default is 0).
If your system has an electronic drain valve, check the drain
duration (system dependent; see the table on Page 74).
More on next page ▶