Installation and Operation Manual
"VUPNBUJDESBJOTFRVFODF"%4
Automatic drain sequence for potable water (not softened)
When configured to run a potable water humidifier with an
automatic drain valve, Vapor-logic
3
uses an automatic drain
sequence (ADS) to help reduce mineral accumulation in the tank
and drain line to decrease tank maintenance.
The ADS sequence starts by opening the drain valve to empty the
tank. The default drain time (ADS duration) is product specific for
potable water (see Table 74-1). Once the drain time expires, the
fill and drain valves remain open to flush the tank. The default flush
time (AFS duration) is one minute. Once the flush timer expires,
the ADS is complete and the humidifier resumes normal operation.
Automatic draining and flushing can be adjusted using the Set Up
screen on the keypad/display. The user can set the drain and flush
duration, and can also set when the draining and flushing occurs.
There are three options (modes) for defining when draining and
flushing occurs:
1. After a user-defined amount of water has been converted to
steam (“Use” mode)
2. At a defined time (“Interval” mode)
3. After a user-defined amount of water has been converted to
steam and at a defined time “Use + Interval” mode)
These three modes are defined in more detail below. Please note
that these options are available only with a standard water system
with an automatic drain valve. If the humidifier is configured for
DI/RO water or if the unit has a manual drain valve, these drain and
flush options are not available.
ADS modes
 6TF
Draining and flushing based on usage is the default ADS mode.
When the ADS mode is set to “Use,” the humidifier enters a
drain and flush sequence after a user-defined amount of water
has converted to steam. For example, if the “Lbs of H2O until
ADS” setup parameter is set to 10,000 lbs (4536 kg) in the Set
Up menu, the humidifier enters a drain and flush sequence the
moment 10,000 lbs (4536 kg) of water convert to steam. This
allows the unit to drain and flush the moment it is needed.
Table 74-1:
System-dependent defaults for
automatic drain sequence (ADS)
Humidifier
ADS duration
(drain time
in minutes)
AFS duration
(flush time
in minutes)
Vapormist 8 1
Humidi-tech 8 1
CRUV 8 1
Vaporstream 12 1
STS 14 1
LTS 14 1
GTS 18 1
VL3_IOM.pdf 78 11/19/2009 9:11:16 AM