DRI-STEEM Vapor-logic
3
*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
51NPEVMBUJPO
TP modulation (electric humidifiers)
The standard form of modulation with an electric humidifier is time
proportioning (TP) modulation. With TP modulation, the outputs
cycle on and off at a certain rate to approximate humidifier demand
as the example below illustrates. To calculate the example, imagine
that each contactor represents 25% of the output of the humidifier.
With a 55% system demand, you need two full contactors plus 5/25
of a third contactor. Therefore, two contactors are full on and a
third contactor is on for 5/25 of 60 seconds, or 12 seconds.
Example
If a Vaporstream humidifier has four heat output stages (four
contactors) and a demand of 55%, two of the contactors are
energized all of the time; one contactor cycles on and off at a certain
rate, and one contactor is off. The rate at which the third contactor
cycles is determined by the demand and the heater cycle time.
Continuing with the example, if you have a heater cycle time of 60
seconds and a demand of 55%, the third contactor cycles at a rate of
12 seconds on and 48 seconds off.
To minimize wear on cycling contactors, Vapor-logic
3
keeps track
of the number of cycles on all contactors, and rotates the TP cycling
contactor to ensure that all contactors get equal wear. In addition,
to prevent short cycling, no contactor has a cycle time less than two
seconds or greater than the heater cycle time minus two seconds.
If system demand dictates that a contactor is on for less than a
second, the contactor does not energize. If the contactor is on
for between one and two seconds, the contactor energizes for the
minimum two-second period. Also, if a contactor is de-energized
for less than one second, it stays on. If a contactor is de-energized
for between one and two seconds, the contactor de-energizes for the
minimum two-second period.
These measures prevent short cycling of the contactors and extend
their life. On a TP system with contactors, the heater cycle time
is user adjustable and can be set from 30 seconds to 99 seconds
(default is 60 seconds) via the Vapor-logic
3
keypad/display.
TP modulation (gas humidifiers)
GTS burners provide TP modulation control when system
demand is low. See Page 7 for more information about gas burner
modulation.