*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
Control input signals
DRI-STEEM offers three control options for all its humidification
systems controlled by Vapor-logic
3
: on-off control, demand signal
control, and transmitter control.
On-off control
On-off control—the simplest control scheme—does exactly what its
name implies: the output device turns fully on, then fully off. Most
residential furnaces use this type of control.
The humidistat that controls the humidifier has a differential
between the on and off switch points. The differential is established
at a range sufficient to prevent output short cycling. In other
words, the humidity level has to fall below set point before the
humidistat closes and energizes the humidifier. Once the humidifier
is energized, the humidistat stays closed until the humidity is
above set point. This creates an operating range that prevents the
humidifier from running for very short periods of time.
In applications where there are multiple contactor outputs, such as
a Vaporstream humidifier, contactors for each heat stage are pulled
in one at a time with a one-second delay between them to prevent
a brownout condition. In applications with a variable output stage,
such as a GTS humidifier, the outputs are ramped up until they
reach 100%.
Demand signal control
With demand signal control, the Vapor-logic
3
controller provides
the output level that a master control signal calls for. This signal
can be generated either by a humidistat or by a building automation
system. The signal sent to the Vapor-logic
3
board is a modulating
signal (typically 4 to 20 mA or 0 to 10 VDC). Vapor-logic
3
responds
to this signal by producing a direct proportional output. In other
words, with a 4 to 20 mA signal, a command of 4 mA produces no
output. A command of 12 mA runs the humidifier at 50% demand,
and a command of 20 mA runs the humidifier at 100% demand.
With a humidistat provided by DRI-STEEM producing this signal,
the humidity set point is set at the humidistat. The keypad/display
then is used for maintaining and troubleshooting the humidification
system, with humidifier control stemming from the humidistat
itself. With a building automation system (BAS) providing the
signal, the humidity set point is established by the BAS, and the
humidifier responds to the BAS commands.